LUCAS MUESUM OF NARRATIVE ART | CAFÉ SERVERY

Los Angeles, CA

Type: Museum Building Size: 300,000 SF

This building includes a café area with a 5,500 SF seating area, 1,800 SF server area, and 4,700 SF production kitchen. The café is designed to serve up to 1,000 people per day or be set up to host private catering events. The servery area consists of four different food selection options, each with their own Type 1 grease hood. The production kitchen has two Type 1 grease hoods and a Type 2 dishwasher hood. There is an 18,000 CFM pollution control unit that removes the grease particles from each Type 1 hood before being exhausted out of the building. There are two 9,000 CFM make-up air handling units that can either heat or cool the incoming outdoor air temperature before being entering the building. These units have fan walls that can operate efficiently over a wide range of capacity to save energy. Air conditioning is achieved thru variable air volume boxes connected to a central chilled water air handing unit that connects to central plant system with heat recovery chillers. The domestic water heating systems can extract excess heat from the central plant system to offset the amount of energy required to heat the hot water system.