AlfaTech HVAC System Strategies for Airborne Diseases
H V A C S Y S T E M S T R A T E G I E S F o r A i r b o r n e D i s e a s e s
AIR DISINFECTION – UVGI DISADVANTAGES
Material Degradation
Some materials degrade under UVC. Sealants, filter material and filter
supports can be impacted on HVAC system.
• Organic filter fibers and Hepa filters have an average of 5-6% weight loss versus fiberglass filter weight loss of 25%
• Other than structural damage, polyester filters may crumble to the touch and lofted fiberglass may irritate eyes (fibers becoming
airborne within ductwork) under UVC exposure.
• UVC resistance ratings shown on Table 8 per ASHRAE RP-1509: A – No effect (aluminum tape, all organic materials
experience mass loss)
B – Minor Effect (mainly cosmetic changes)
C – Moderate Effect (some cracking/pitting)
D – Severe Effect (structural damage, not recommended)
Courtesy of Table 8, ASHRAE RP-1509
Made with FlippingBook Ebook Creator