Engineering Strategies for Airborne Diseases
H V A C S Y S T E M S T R A T E G I E S
AIR DISINFECTION – UVGI DISADVANTAGES
Material Degradation
Some materials degrade under UVC. Sealants, filter material and filter supports can be impacted on HVAC system. • Organic filter fibers and Hepa filters have an average of 5-6% weight loss versus fiberglass filter weight loss of 25% • Other than structural damage, polyester filters may crumble to the touch and lofted fiberglass may irritate eyes (fibers becoming airborne within ductwork) under UVC exposure. • UVC resistance ratings shown on Table 8 per ASHRAE RP-1509:
A – No effect (aluminum tape, all organic materials experience mass loss)
B – Minor Effect (mainly cosmetic changes)
C – Moderate Effect (some cracking/pitting)
D – Severe Effect (structural damage, not recommended)
Courtesy of Table 8, ASHRAE RP-1509
Made with FlippingBook Publishing Software